      一、Overview

      1.1 Purpose and scope of application

      The rectifier transformer (hereinafter referred to as transformer) is a dry transformer that mainly applies to the urban trolleybus traction substation.

      1.2  Model composition and its meaning

      Rated input voltage

      Rated power

      Design Number

      Three-phase transformer

      Apply to the traction substation

      Rectifier transformer 


      1000KVA/10000V Main technical parameters of rectifier transformer

      capacity

      (KVA)

      Model and specification

      Transformation ratio

      (KV)

      Connection group

      No load loss

      (W)

      Load loss

      (W)

      impedance

      %

      No load current

      L

      (mm)

      B

      (mm)

      H

      (mm)

      63

      ZQS11-63

      10±2*2.5%/0.47

      Y/d-11

      350

      680

      5

      2.5

      1130

      596

      1055

      100

      ZQS11-100

      10±2*2.5%/0.47

      Y/d-11

      500

      1050

      5

      2.5

      1095

      707

      1100

      400

      ZQS11-400

      10±2*2.5%/0.47

      Y/d-11

      1350

      3000

      5

      1.8

      1385

      742

      1440

      630

      ZQS11-630

      10±2*2.5%/0.47

      Y/d-11

      1800

      4100

      5

      1.5

      1493

      868

      1585

      1000

      ZQS11-1000

      10±2*2.5%/0.47

      Y/d-11

      2350

      6100

      5

      1.2

      1380

      1100

      1226

      1250

      ZQS11-1250

      10±2*2.5%/0.47

      Y/d-11

      2800

      7100

      5

      1.0

      1966

      1116

      2072


      1.3 Product parameters 

       Table 1

      Rated capacity

      kVA

      Voltage on line side

      kV

      Voltage on valve side

      kV

      Group number of jointing

       Short-circuit impedance

      Grade of load

      Remark

      1000

      6±2*2.5﹪

      0.470

      Y/d-11

      5﹪

      1.2Ⅴ

       

      1.4  Application environment and operating condition

      1.4.1  

      The transformer is applied to places free from harmful gases that may corrode metal and compromise insulation, gas, coal dust or other similar places.

      1.4.2 The elevated altitude shall not exceed 1000m.

      1.4.3 The temperature for the surrounded medium shall not exceed +40℃ and lower than -20℃.

      1.4.4The relative humidity of the surrounded medium shall not exceed 95%(when the air temperature is 20℃±5℃).

      1.4.5 It shall be kept at places free from water and other liquids.

      1.4.6 It shall be kept at places free from severe vibration and impact.

      1.4.7 The horizontal slope of the installation place shall not exceed 5%.

      1.4.8 :The requirements to the line side power supply:

       a) Phase number and frequency:

             b) The fluctuation range of voltage magnitude: the continuous fluctuation shall not exceed 10% of the rated value.

             c) The variation range of frequency; it shall not exceed 2% of the rated value.

             d)

      The degree of symmetry: the negative sequence or zero sequence component shall not exceed 5% of the positive sequence component.

      I. The design principle and structural features of the transformer

      2.1  The design principle of the transformer

      1min, As the transformer is mainly applied to the traction substation, therefore, it must satisfy the overload requirement of its rectifier, which means that it can continue to operate for 100% of rated output current, and it can operate continuously for 2h for 150% of the rated output current and it can operate continuously for 1h for 200% of the rated output current.

      2.2  The installation of transformer

      It should be separately installed indoor.

      2.3 The technical performance of the transformer

      2.3.1 Rated capacity: Please refer to table 1;

      2.3.2 The rated voltage on line side and on valve side: Please refer to table 1;

       2.3.3 The tapping mode: A tap is available at the position of ±2*2.5﹪

      2.3.4 Grade of load: V

      2.3.5 Insulation grade: F

      2.3.6 Ultimate temperature rise: 80K

      2.3.7Type of cooling: Natural air cooling.

      2.3.81min;Insulation level: 6kV voltage class and withstand power frequency voltage is 20kV, duration 1min

      2.3.9 Short-circuit impedance: Please refer to table 1;

      2.3.10 The no-load voltage ratio measured shall not be greater than ±1﹪ of the specified value;

      2.3.11 The no-load loss, load loss and the no-load current shall conform to the stipulation of GB/T 10228.

      2.3.12 DC:600V; The DC rated output voltage:

      2.3.13 DC1250A; The DC rated output current:

      2.3.14 Digital temperature controller is available for the product

      2.3.15  Operating mode: continuous

      2.3.16  Cooling mode: self-cooling

      2.3.17 Without outer shell.

       

      II. The installation and operation of transformer

      3.1 Please make sure that the winding and the iron core of the transformer shall be secured and make sure that there is no damage of its wire insulation. Please make sure that the screws of upper and lower clamping plate shall be secured, please eliminate any abnormal condition.

      3.2 Before connecting to the power supply, please use the ground bolt of the transformer to ground it well. Then, use a tramegger to measure the insulation resistance of three windings to the iron core and the primary and secondary insulation resistance of each winding. The resistance of 6kV voltage shall be no less than 10 MΩ and shall be no less than 1MΩ for 1KV voltage or lower voltage.

      3.3  Please connect the wire for transformer to the power supply for once and connect the wire for transformer to the rectifier for twice according to the instruction on the label of the transformer. Please do not switch primary and secondary winding, otherwise, the transformer and rectifier may be severely damaged.

      3.4 Please use voltmeter to measure the three-phase voltage twice once electrifying and make sure that the degree of symmetry shall not be greater than 5%. Please make sure that the voltage value shall meet the requirements of the output of rectifier, if not, please adjust it through tapping point.

      3.5 Please pay attention to the temperature rise of the winding for the first operation, if the temperature is too high, please shut down the power supply for inspection.

      III. Fault analysis and troubleshooting

       

      Faults

      Reason analysis

      Troubleshooting

      Remark

      Winding wire package overheat or discoloring, the feeder switch may trip for more severe condition

      1、The excessive overload or long-time DC output;

      2、Short circuit caused by the input circuit leakage

      3 、Short circuit between turns of windings

      1、Wrong model

      2、;Check the circuit

      3、Replace or repair

      Contact the manufacturer

      Overheating of the iron core and clamp

      1、;Insulation damage of core silicon steel sheet

      2、The insulation damage of fastening stud and clamping plate and iron core

      1、Replace part of the silicon steel sheet or rewire assembly

      2、  Check whether the casing of stud or sleeve gasket is damaged, please replace or repair

      Contact the manufacturer

      Excessive noise after electrifying

      1、The iron core fails to be clamped tightly

      2、Loose winding

       

       Clamp tightly

      Contact the manufacturer

       

      IV. Maintenance

      5.1The dry transformer is a product of high reliability and it normally can operate well with less fault. For overhaul and recondition, please observe whether there are any abnormal conditions of the windings or measure the insulation resistance. Please use clamp meter to measure the three-phase input current on the line side when re-electrifying, please process accordingly for any abnormal conditions.  

      5.2 The storage environment and re-boot requirements

      Please keep the transformer in places are dry, free from rain and of good ventilation if not use it in a long time. Please proceed according to the third point to install to use.


      聯(lián)系方式

      No. 139-44, wumuquan street, Wuqi, Xinjiang

      期待你的來電

      搜了網(wǎng)提醒您:
      1、本信息由搜了網(wǎng)用戶發(fā)布,搜了網(wǎng)不介入任何交易過程,請(qǐng)自行甄別其真實(shí)性及合法性;
      2、跟進(jìn)信息之前,請(qǐng)仔細(xì)核驗(yàn)對(duì)方資質(zhì),所有預(yù)付定金或付款至個(gè)人賬戶的行為,均存在詐騙風(fēng)險(xiǎn),請(qǐng)?zhí)岣呔瑁?

      相關(guān)資訊

      在線給我留言
      免費(fèi)開通商鋪
      掃碼關(guān)注電氣網(wǎng)
      服務(wù)熱線
      4008-635-735

      
      

      <strong id="tw5rd"><acronym id="tw5rd"><th id="tw5rd"></th></acronym></strong>

        在线a片免费观看 | 黄色短文小说 | 96亚洲精品久 | 日本人的性生活视频 | 性欧美freesex顶级少妇 | 激情黄色五月天 | 校花被操在线观看 | 秋霞一区二区三区四区 | 干人人 | 青春草久久 |